Xylem IM223 R04 Hydrovar Pump Control Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Bombas Xylem IM223 R04 Hydrovar Pump Control. Xylem IM223 R04 Hydrovar Pump Control User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - Hydrovar Pump Control

Hydrovar Pump ControlINSTALLATION, OPERATION AND MAINTENANCE MANUALINSTRUCTION MANUALIM223R04

Página 2

10Section 4Hydrovar Variable Speed Drive Type and Catalog NumberHydrovar Example Product Code HV M 3 4 20 0Filter (optional): Standard = 0, (no

Página 3

11Section 4 (continued)Hydrovar Product Numbering ChartMODEL NUMBER CODEVoltage Phase Normal Duty HP Drive Type Model Number230 V 12MASTER HVM1202BASI

Página 4 - Pressure

12Section 5TECHNICAL DATAHydrovar Power SupplyRated Output Voltage Limits 48-62 HZRated Current InputRecommended Line ProtectionMaximum Wire SizeCat

Página 5

135.1 General Technical Data Ambient temperature: 0° C ... +40° C, 32º F... +104º F At higher temperatures reduce the output current as shown be

Página 6 - SYSTEM DESIGN

145.2 EMC Requirements (Electromagnetic Compatibility)The EMC requirements depend on the intended use.Class B environment (EN 61800-3: Class C2)Enviro

Página 7 - PRODUCT OVERVIEW

15Section 6HVM1202, HVM1203, HVM3403, 3405 All dimensions in inches! Drawings are not to scale! Dimensions are nominal Type Weight [lbs] Basic

Página 8

16HVM3407, HVM3410, HVM3415 All dimensions in inches! Drawings are not to scale! Dimensions are nominal Type Weight [lbs] Basic Master / Sin

Página 9

17Section 77.1 Cable Glands Provided7.2 Assembly Instructions – All modelsTo remove the HYDROVAR cover, loosen the 4 fastening screws.• Verify that th

Página 10 - Section 4

187.2 Assembly Instructions – All models (continued)ADDITIONAL COMPONENTS

Página 11 - MODEL NUMBER CODE

19Section 8NOTEAll installations and maintenance must be performed by properly trained and qualied personnel. Use personal protection equipment.NOTEI

Página 12 - TECHNICAL DATA

21 Important Safety Instructions ...

Página 13

20Fused Disconnect Box:GNDL1L2135246SINGLEPHASECUSTOMER SUPPLIEDVOLTAGEDISCONNECTFUSE BLOCK12 AWG12 AWGHYDROVARGNDPEU1V1W1U2V2W216 AWGGNDMTRMOTORCUSTO

Página 14 - may be required

218.2 EMC – Electromagnetic CompatibilityTo ensure electromagnetic compatibility the following points must be observed for cable installation:Control

Página 15 - DIMENSIONS AND WEIGHTS

228.3 Recommended Wire TypesFor maximum 40º C ambient temperature, recommend use of 75º C wire of the following types: RHW, THHW, THW, THWN, XHHW, US

Página 16

238.4.1 Input Voltage TerminalsThe power supply is connected to the power section:Terminal L + N (230 VAC, single-phase)Terminal L1+ L2 + L3 (460 VA

Página 17 - ADDITIONAL COMPONENTS

248.4.2 Motor ConnectionAttaching the Thermistor Method A : Method B :1. Remove conduit box cover2. Attach the thermistor (Method A or B)3. Replace

Página 18

25X1 Control terminals – power unit PTC Terminals have Jumper between them. Remove jumper and attach Thermistor leads SL SOLO RUN (Hand Mode) S

Página 19 - Section 8

26Connection Example External switch to enable the SOLO RUN (Hand Mode) Example: Low water or other emergency off switch Thermistor (mounted in

Página 20 - CUSTOMER SUPPLIED

27Terminating Control Wires:- Use recommended cable type (see section 8.2)- Strip the end of the wire aproximately 1/4"- Push down the orange wed

Página 21

28Setting the correct address on Basic drives:• The HYDROVAR must be disconnected from power supply for at least 5 minutes before removing the top cov

Página 22

29 X3 Digital and Analogue I/O X3/ 1 GND, electronic ground 2 Actual value current input sensor 1 0-20mA / 4-20mA [Ri=50Ω] 3 Power supply

Página 23

39 Programming ...

Página 24

30 Additional power supply ** max. 100 mA Current signal input (required val. 2) 0-20mA / 4-20mA [Ri=50Ω] To determine the required value or the of

Página 25

31Connection Examples:• Sensor–Actual-value-signal Input Connecting a 3-wire transducer Connecting an active actual-value-signal (e.g. standard pres

Página 26

32}}• Switching between two different required valuesExternal switching between two connected required value signals (e.g.: between voltage and curren

Página 27

33 RS-485 – Internal interface RS-485 - User interfaceThe internal RS-485 Interface is used for communicating between up to 8 HYDROVARs in a multi-p

Página 28 - 1 2 3 4

34X5 Status-Relays X5/ 1 CC 2 Status Relay 1 NC [Max. 250VAC] [250mA] 3 NO [Max. 220VDC] [250mA] 4 CC [Max. 30VDC] [2A] 5 Status

Página 29 - 0-20mA / 4-20mA [Ri=50Ω]

35Section 9NOTERead and follow the operating instructions carefully before programming to avoid incorrect settings which will cause drive errors! All

Página 30 - Low water

369.3 Basic Drive Display Status LED - green Constant Motor stopped (Standby) Blinking Motor run Error LED - red The type of error is indicated

Página 31 - Digital Input 1

37Parameters which are available on all HYDROVAR drives are marked with the following symbol:… “global” parameter (available on all HYDROVAR drives)NO

Página 32

38 ON Running Stop the HYDROVAR by pressing ▼ STOP Manually stopped Start the HYDROVAR by pressing ▲ OFF E-Stop (X3/7-8) is open To start

Página 33 - HYDROVAR User Interface

39Parameter [03] is not used in Mode: Actuator 04 04 START VALUE Regulation Restart Value OFF Possible settings: 0 – 99 % – OFFThis parameter de

Página 34

4DANGERSection 1Important: Read all safety information prior to installation of the Controller.NOTEThis is a SAFETY ALERT SYMBOL. When you see this sy

Página 35 - PROGRAMMING

40 08 08 AUTO - START Auto Start ON Possible settings: ON – OFFSelect ON with ▲ or OFF with the ▼ button.If AUTO-START = ON the HYDROVAR starts a

Página 36

41 22 22 SELECT DEVICE Select device * 1 * Possible settings: 1-8Check the current status, the motor hours and the most recent failures of any g

Página 37

42GG 24 24 ENABLE DEVICE Enable – Disable of the selected device Enable Possible settings: Enable - DisableAllows the drive to be be enabled or

Página 38

43GGGGGG 40 40 SUBMENU DIAGNOSTICS 41 41 PROD. DATE production date of the HYDROVAR (Master/Single only) XX.XX.XXXXIn the following parameters

Página 39

44 60 60 SUBMENU SETTINGSNOTECarefully read these instructions before changing the remaining parameters. Improper settings can cause the drive to mal

Página 40

45Controller (Default Setting):Select this mode when only one HYDROVAR Master/Single Drive is used and there is no connection to any other HYDROVAR vi

Página 41

46In actuator mode the drive can work with pre-selected frequencies for manual control of the HYDROVAR. Two different frequencies can be set in the su

Página 42

47GSGSOFF: All parameters in the MAIN menu (only) can be changed without entering the password.ON: If the LOCK FUNCTION is activated, no changes can b

Página 43

48If several HYDROVAR Master Inverters and even Basic Inverters are connected via the RS-485 interface, the parameters in SUMBENU [200] can be entered

Página 44

49GGG 0215 0215 RAMP 1 Ramp 1: Fast acceleration time 4 sec Possible settings: 1 – 250 (1000) sec• Rapid acceleration may cause an error (OVER

Página 45

5HazardousPressureCAUTIONSection 2The following diagrams show typical single and multi-pump systems using the HYDROVAR Variable Speed Drive. Connect d

Página 46

50GGGGG 0245 0245 MAX. FRQ. Maximum frequency 60 Hz Possible settings: 30.0 – 70.0 HzThis parameter determines the maximum frequency output to

Página 47

51GGG 0270 0270 KNEE FRQ. Knee frequency 60.0 Hz Possible settings: 30.0 – 90.0 HzThis parameter determines the frequency at which the HYDROVA

Página 48

52GGGG 0285 0285 SKIPFRQ CTR Skip frequency start point 0.0 Hz Possible settings: fmin - fmax 0286 0286 SKIPFRQ RNG Skip frequency range 0

Página 49

53GGHQAC01234Bf = 100%%f%f%fG 0320 0320 REG. MODE Regulation mode normal Possible settings: normal, inverseNormal: Speed is increased with fal

Página 50

54 0400 0400 SUBMENU SENSORIn this submenu all actual value sensors which are connected to the HYDROVAR can be congured, (up to two transducers wi

Página 51

55 0415 0415 SENSOR TYPE Selection of the sensor type and input terminal 4 – 20mA Possible settings: - analog I 4-20mA - analog I 0-20mA - ana

Página 52

56SSSHQ00P 1 P 1+2 P 1 +2+3 0440 0440 SENS 2 CAL 0 Sensor 2 zero point calibration 0% = actual value Possible settings: - 10% up to +10%Zero poi

Página 53

57GGGSSSSSCalculations of the new required value for multi pump applications:k ... number of active pumps (k >1)p = pset + (k-1)*[lift value – fall

Página 54

58SSSSS 0530 0530 DISABLE FRQ Disable frequency (for cascade relay only!) 30 Hz Possible settings: 0.0 – 120.0 HzThe frequency to switch off the

Página 55

59GSGGGSSS 0555 0555 SWITCH INTV Switch interval for lead / lag alternation 24 hours (for cascade serial / synchron only!) Possible settings:

Página 56 - P 1 P 1+2 P 1 +2+3

6Pressure Tank, Pressure Relief Valve and Discharge PipingUse only “pre-charged” tanks on this system. Do not use galvanized tanks. Select an area tha

Página 57

60GGON - all Master Inverters in the system start (unless it is stopped manually or by a failure) before the rst Basic Inverter runs.For example: Ad

Página 58

61SSNot all errors can be reset automatically. (For detailed information see chapter 10 failure messages)OFF: if the ERROR RESET is set to OFF, each f

Página 59

62SSS 0800 0800 SUBMENU REQUIRED VALUES 0805 0805 C.REQ.VAL 1 Conguration required value 1 digital Possible settings: - digital - analog U

Página 60

63S 0815 0815 SW REQ. VAL Switching between required value 1 and 2 Setpoint 1 Possible settings: - Setpoint 1 - Setpoint 2 - Switch Dig 1 -

Página 61

64SSSSSSSS 0900 0900 SUBMENU OFFSETThe Offset function allows for a change in setpoint based on a separate process parameter, (ex., ow rate). Use of

Página 62

65S 0918 0918 OFFSET Y2 Desired value 0.00 PSI Possible settings: 0 – standardization of the sensorDesired value; designation of the y – coordin

Página 63

66SGGGG 1000 1000 SUBMENU TEST RUN 1005 1005 TEST RUN Automatic test run after 100 hrs Possible settings: OFF – 100 h.The Automatic Test Run

Página 64

67 1100 1100 SUBMENU SETUP 1110 1110 FACTORY SET Restores the HV to factory setting USA Possible settings: EUROPE, USATo restore the HYDROVAR to

Página 65 - Required Value

68S 1210 1210 BAUDRATE Baudrate for user interface 9600 Possible settings: 1200, 2400, 4800, 9600, 14400, 19200, 38400 1215 1215 FORMAT Format f

Página 66

69Section 10NOTEIf the HYDROVAR is stopped by an error (warning), the HYDROVAR and the motor remain under voltage. Before any work is carried out on t

Página 67

7Section 33.1 Hardware CongurationsThe HYDROVAR variable speed drive consists of two separate components: the power unit and the control card. In its

Página 68

7010.2 Master / Single InverterEach error is shown on the display in plain text and saved in the error memory.The errors can be reset automatically (d

Página 69 - FAILURE MESSAGES

71 Error Probable Cause Measure • Check Parameter RAMP 1/2 [0215 / 0220] (too short) and BOOST [0265] (too low) OVERLOAD

Página 70

72SS • Incoming pressure or minimum level too low LACK OF WATER Low water contact • Bridge X3/11-12, if there is no ext. ERROR 21 (X3/

Página 71

7310.3 Internal ErrorsTo remove the following errors cut the power supply for >60 seconds. If the error message is still shown on the display, cont

Página 72

74Control on Constant Flow Problem: Control Fluctuations Cause: Check: • Increase WINDOW [0310] and set Control characteristics are set too low

Página 73 - ⇒ change control card

75Section 11 – MaintenanceThe HYDROVAR does not require any special maintenance. However, the cooling fan and the vents should be free of dust. Also t

Página 74

76Section 120 MAIN MENU20 SUBMENUSTATUS0 MAIN MENUXYLEM xx.x Hz 50 PSI2 REQUIRED VAL 50 PSI6 DATE xx-xx-20xx22 SELECT DEVICE * 01 *42 SEL.

Página 75 - MAINTENANCE

77PROGRAMMING FLOW CHARTSection 12 (continued)100 SUBMENUBASIC SETTINGS200 SUBMENUCONF INVERTER300 SUBMENUREGULATION400 SUBMENUSENSOR500 SUBMENUSEQUEN

Página 76 - PROGRAMMING FLOW CHART

781000 SUBMENUTESTRUN800 SUBMENUREQUIRED VALUES700 SUBMENUOUTPUTS1000 SUBMENUTESTRUN1100 SUBMENUSETUPS1100 SUBMENUSETUPS605 MIN.THRESH. disabled705 A

Página 78

8Application ExampleBooster sets up to 6 pumps where only one pump is speed controlled by the HYDROVAR and the others are xed speed (1 HYDROVAR Maste

Página 79

LIMITED WARRANTYThis warranty applies to this Xylem Inc. product.Any part or parts found to be defective within the warranty period shall be replaced

Página 80

9To increase the reliability of a system, (in the event of a Master controller failure) a second Master controller can be used.Full-featured possibili

Comentários a estes Manuais

Sem comentários