Xylem ADAQCPC Modbus Aquavar CPC Manual do Utilizador Página 8

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 20
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 7
8
0XXXX MAPPING MODBUS COILS / AQUAVAR CONTROL WORD
Modbus Ref. Internal Location R/W Command Value Notes:
00001 Control Word - Bit 0 R/W STOP
1 = STOP,
0 = (no op)
STOP Bit Must be
set to 0 to start
drive via Modbus.
If both STOP and
START are set to 1,
drive will stop or
remain stopped.
00002 Control Word - Bit 1 R/W START
1 = START,
0 = (no op)
00003 Control Word - Bit 2 n/a Reserved (Not Used)
00004 Control Word - Bit 3 n/a Reserved (Not Used)
00005 Control Word - Bit 4 R/W RESET
1 = RESET,
0 = (no op)
00006 Control Word - Bit 5 R/W EXT2
1 = EXT2,
0 = EXT1
00007 Control Word - Bit 6 n/a Reserved (Not Used)
00008 Control Word - Bit 7 n/a Reserved (Not Used)
00009 Control Word - Bit 8 n/a Reserved (Not Used)
00010 Control Word - Bit 9 n/a Reserved (Not Used)
00011 Control Word - Bit 10 n/a Reserved (Not Used)
00012 Control Word - Bit 11 n/a Reserved (Not Used)
00013 Control Word - Bit 12 n/a Reserved (Not Used)
00014 Control Word - Bit 13 n/a Reserved (Not Used)
00015 Control Word - Bit 14 n/a Reserved (Not Used)
00016 Control Word - Bit 15 n/a Reserved (Not Used)
00017 Control Word - Bit 16 n/a Reserved (Not Used)
00018 Control Word - Bit 17 n/a Reserved (Not Used)
00019 Control Word - Bit 18 n/a Reserved (Not Used)
00020 Control Word - Bit 19 n/a Reserved (Not Used)
00021 Control Word - Bit 20 n/a Reserved (Not Used)
00022 Control Word - Bit 21 n/a Reserved (Not Used)
00023 Control Word - Bit 22 n/a Reserved (Not Used)
00024 Control Word - Bit 23 n/a Reserved (Not Used)
00025 Control Word - Bit 24 n/a Reserved (Not Used)
00026 Control Word - Bit 25 n/a Reserved (Not Used)
00027 Control Word - Bit 26 n/a Reserved (Not Used)
00028 Control Word - Bit 27 n/a Reserved (Not Used)
00029 Control Word - Bit 28 n/a Reserved (Not Used)
00030 Control Word - Bit 29 n/a Reserved (Not Used)
00031 Control Word - Bit 30 n/a Reserved (Not Used)
00032 Control Word - Bit 31 n/a Reserved (Not Used)
00033 Not used in CW R/W RELAY OUTPUT 1
1 = Energize,
0 = Denergize
00034 Not used in CW R/W RELAY OUTPUT 2
1 = Energize,
0 = Denergize
00035 Not used in CW R/W RELAY OUTPUT 3
1 = Energize,
0 = Denergize
00036 RESERVED n/a Reserved (Not Used)
00037 RESERVED n/a Reserved (Not Used)
00038 RESERVED n/a Reserved (Not Used)
Supported Function Codes
01 - Read Coil Status 05 - Force Single Coil 15 - Force Multiple Coils (0x0F Hex)
Vista de página 7