Xylem CHATTER Hardware Manual Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Equipamento Xylem CHATTER Hardware Manual. Xylem CHATTER Hardware Manual User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - Data Logger

Hardware Installation and User ManualData LoggerData Logger1GB Chatter Hardware Manual 100416

Página 2

USBTESTSWUSBSIM cardON OFFBatteryANT.1ANT.2ANT.3DI 1DI 2DI 3DI 4AI 1AI 2AI 3AI 4GNDGND+5/ 10/ 15VGND3V6-AGNDGNDABGND3V6-BGNDRS485123453.6 VDC battery

Página 3 - Table of Contents

Analog Inputs (2)Chatter has four analog inputs each with a range of 0,1 - 2,5 VDC (see posi-tion “2” on the drawing to the left).Analog inputsTermina

Página 4

Serial Data Communication for Modbus (5)Chatter is equipped with RS-485 serial data communications. See position “5” in Figure 2.RS-485 Serial Data Co

Página 5 - 1. Introduction

Antenna Connector ANT.1 (10)Connector no. 1 is designated for a standard GSM/GPRS antenna. Antenna Connector ANT.2 (11)Connector no. 2 is designated f

Página 6 - 2. Safety and Repair

This page is left blank.Data Logger14GB Chatter Hardware Manual 100416

Página 7 - Specifications

5. MountingMJK Chatter data logger is supplied in two different mounting versions: one for pipe mounting and one for wall mounting (mounting on wall o

Página 8 - Accessories

4. Secure stud bolts and wedges with a rubber band as shown below.3.4.Figure 4. Secure Stud Bolts and Wedges with a Rubber Band5. Immerse the Chatt

Página 9 - 4. Electrical Connections

7. Tighten the screws with a 7 mm spanner until the base is bolted onto the pipe:7.Figure 7. Tighten the Screws with a SpannerFrom here on the base

Página 10 - Digital Inputs (1)

9. Remove the protective sleeving from the pressure transmitter and immerse the pressure transmitter in the pipe.9.Figure 9. Immerse the Pressure Tr

Página 11 - Voltage Outputs (4)

11. Mount the Chatter top on the base by turning the top approx. 1 cm counter-clockwise, until the holes for the security padlock align. Expect a sli

Página 12 - Booster Capacitor (8)

Declaration of ConformityData LoggerData LoggerKonformitetserklæringVi, MJK Automation A/S, DK-2850 Nærum, påtager os det fulde ansvar for at produkte

Página 13 - TEST SW (13)

5.2 Wall Mounting1. Mount the cabinet on the wall.2. Connect the pressure transmitter(s) according to the example in section 8.1 MJK Chatter and M

Página 14

6. Gain Access to SIM Card and BatteryTo change SIM card or battery in a Chatter unit, you must gain access to the unit’s circuit board.6.1 Pipe Moun

Página 15 - 5. Mounting

9. Re-connect the pressure transmitter connector by turning the union clock-wise.10. Immerse the pressure transmitter into the pipe, and make sure th

Página 16

6.2 Wall Mounting1. Locate the Chatter unit: Figure 15. Wall Mounted Chatter in Custom-designed Cabinet2. Loosen the four screws in the top cover

Página 17

This page is left blank.Data Logger24GB Chatter Hardware Manual 100416

Página 18

7. Internal Installation in the Chatter Unit7.1 Inserting a SIM Card1. Open the Chatter unit to gain accesss to the circuit board and the SIM card h

Página 19

3. Carefully insert the SIM card into the grooves that hold the card, and finally push it to the end stop. IMPORTANT: The SIM card must align with the

Página 20 - 5.2 Wall Mounting

7.2 Battery Change1. Open the Chatter unit to gain accesss to the circuit board and the bat-tery as described in section 6. Gain Access to SIM Card

Página 21 - 6.1 Pipe Mounting

This page is left blank.Data Logger28GB Chatter Hardware Manual 100416

Página 22

8. Connection Examples8.1 MJK Chatter and MJK Expert TransmitterDK 2.76 Expert 7060/7070 090120ww w.mjk.comDK: +45 45 56 06 56NO: +47 69 20 60 70SE

Página 23 - 6.2 Wall Mounting

Data Logger3Table of Contents1. Introduction 52. Safety and Repair 6Safery Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 24

8.2 MJK Chatter and Digital InputUSBUSBSIM cardON OFFBatteryANT.1ANT.2ANT.3DI 1DI 2DI 3DI 4AI 1AI 2AI 3AI 4GNDGND+5/ 10/ 15VGND3V6-AGNDGNDABGND3V6-B

Página 25 - 7.1 Inserting a SIM Card

9. Physical ActivationThe Chatter unit is activated physically by moving the jumper shown on page 12 and in the figures below from position ”OFF” to po

Página 26

This page is left blank.Data Logger32GB Chatter Hardware Manual 100416

Página 27 - 7.2 Battery Change

10. Mechanic DimensionsChatter Unit for Pipe Mounting150 mm101 mm190 mmØ 63 - 106 mmIndre rørdiameter190150101Inner pipe diameterØ63 - Ø106Figure 24.

Página 28

This page is left blank.Data Logger34GB Chatter Hardware Manual 100416

Página 29 - MJK Expert™ 7060 / 7070

11. Maintenance The MJK Chatter Data Logger requires no maintenance.Service AgreementA service agreement guaranties the equipment’s long term reliabil

Página 30 - ”active”

This page is left blank.Appendix A. Frontpanel Cut-Out TemplateThe dotted lines indicate the front panel contour and measures 155 x 145 mm.Cut-out ar

Página 31 - 9. Physical Activation

Appendix A. Frontpanel Cut-Out TemplateThe dotted lines indicate the front panel contour and measures 155 x 145 mm.Cut-out areaFrontpanel outlineUpAp

Página 32

This page is left blank.Data Logger38GB Chatter Hardware Manual 100416

Página 33 - 10. Mechanic Dimensions

Appendix B. Calculation of Battery LifetimeThe battery in the MJK Chatter unit is of the lithium-trionyl-ion-trotyl type which is characterized by a

Página 34

9. Physical Activation 3110. Mechanic Dimensions 33Chatter Unit for Pipe Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 35 - 11. Maintenance

Calculation Example 1 Chatter basic consumption per day (fixed) = 1.0No. of logs per day @sensor consump.=2mA 1 x 0.1 = 0.1No. of log

Página 36 - Frontpanel outline

Calculation Example 3 Chatter basic consumption per day (fixed) = 1.0No. of logs per day @sensor consump.=2mA 24 x 0.1 = 2.4No. of lo

Página 37

This page is left blank.Data Logger42GB Chatter Hardware Manual 100416

Página 38

Appendix C. Calculation of WLD- and Ref. DatumThe following examples illustrate how you can calculate the water level datum (WLD) in relation to the

Página 39 - Calculation Template

The water level datum (WLD) in this example: 34.76 - 24.9 + 7.65 => 17.51 mThe following figures/numbers for the bore are required as entries to the

Página 40 - Calculation Example 2

List of FiguresFigure 1. Opening the Chatter Unit for Pipe Mounting 9Figure 2. Terminal Blocks for Signal Inputs, Voltage Outputs and Serial Commun

Página 41 - Calculation Example 3

This page is left blank.Data Logger46GB Chatter Hardware Manual 100416

Página 42

IndexAaccesssories . . . . . . . . . . . . . . . . . . 8accuracy . . . . . . . . . . . . . . . . . . . . . 7activation . . . . . . . . . . .

Página 43

service agreement . . . . . . . . . . . . . 35SIM card . . . . . . . . . . . . . 7, 12, 21, 25specifications . . . . . . . . . . . . . . . . . .

Página 44

This page is left blank.Data LoggerIndex-3GB Chatter Hardware Manual 100416

Página 45 - List of Tables

1. IntroductionThank you for choosing MJK Chatter™ Data Logger. We have done our best to design and produce a quality data logger to meet your require

Página 46

LiabilityMJK Automation A/S are liable to the common rules of Da-nish law on product liability, however, the liability is reduced to coverage of our p

Página 47

2. Safety and RepairSafery Instructions• Read this manual thoroughly• Be aware of the environment at the installation site. Be sure to use the neces

Página 48

3. Specifications, Order Numbers and AccessoriesSpecificationsSpecificationsDigital inputs 4 pcs. 2 - 5 VDC (shortest interval 1x per count. 10 seconds)A

Página 49

Order NumbersOrder Numbers204105 Chatter™ GSM / GPRS for pipe mounting204106 Chatter™ GSM/GPRS/GPS for pipe mounting204110 Chatter™ GSM / GPRS for wal

Página 50

4. Electrical ConnectionsAccess the electrical connection terminals of the Chatter unit, the SIM card and the battery as follows: 1. Open and remove