For Series 42S Low Water Cut-Off/
Pump Controllers (All Models)
Replacement Snap Switch Assembly
SWA-42S
Before using this product read and understand instructions.
Save these instructions for future reference.
All work must be performed by qualified personnel trained in the proper application, instal-
lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be
0 psi (0 bar) before servicing.
To prevent electrical shock, turn off all sources of electrical power before servicing unit.
This low water cut-off must be installed in series with all other limit and operating controls
installed on the boiler. After servicing unit, check for proper operation of all of the limit and
operating controls before leaving the site.
To prevent a fire, do not use this low water cut-off to switch currents over 7.4A, 1/3 Hp at
120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.
Failure to follow this warning could cause property damage, personal injury or death.
W
A
R
NIN
G
C
AU
TION
!
WARNING
Replacement Switch Assembly
INSTRUCTION MANUAL
MM-244B
Vista de página 0
1 2 3 4 5 6 ... 11 12

Resumo do Conteúdo

Página 1 - INSTRUCTION MANUAL

For Series 42S Low Water Cut-Off/Pump Controllers (All Models)Replacement Snap Switch AssemblySWA-42S• Before using this product read and understand i

Página 2

10RULERCASTLINELEVEL3"(76.2mm)2"(50.8mm)1"(25.4mm)CastingCut-OffLine1"(25.4mm)TOPSECTION 3 - Checking Switch Settings at 0 Pressur

Página 3 - OPERATION

11B6. Reattach the cover (B).OFFON7. Turn the boiler on.2"(50.8mm)1"(25.4mm)1"(25.4mm)3"(76.2mm)CastingCut-OffLineSwitch Level Rul

Página 4 - INSTALLATION –

Xylem Inc. 8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379www.xyleminc.com/brands/mcdonnellmillerMcDonnel

Página 5

2Verify that you have the Correct Replacement Switch Assembly ModelModel SWA-42SP/N 310488IMPORTANT:• Installation of an incorrect switch-assembly cou

Página 6

Pump Circuit Rating (Amperes)Voltage Full Load Locked Rotor Pilot Duty120 VAC 7.4 44.4345 VA at240 VAC 3.7 22.2120 or 240 VACApproximateDistance Above

Página 7 - Operating Pressure

4B3. Remove the cover (B).LOW WATERCUT-OFFTERMINALSBURNERSWITCHPUMPSWITCHPUMP CIRCUITTERMINALS4. Mark and remove the pump switchand burner/alarm switc

Página 8 - AT CAST LINE

5BA5a. Locate the actuator assembly (A) and thetwo fillister head screws (B) which secureit to the bearing of the control.b. Clean the inspection lacq

Página 9 - " (19mm)

6CC8a. Install the new switch bracket assemblyinto the junction box in the same orienta-tion as the old switch bracket assembly(i.e. with arrows on th

Página 10 - (Not to Scale. Template

7SECTION 2 - Checking Switch Settings and Adjusting Switch Setpoints atOperating PressureIMPORTANT: All switches have fixed differentials.Adjustment o

Página 11 - 7. Turn the boiler on

FADD ADHESIVE HERE8BURNERSET SCREWBURNERSWITCHE4b. If the cut-off point does not match the oneshown in chart for the control (page 3) asmeasured on th

Página 12 - Xylem Inc

9PUMPONPUMPOFFBURNERCUT-OFF LEVELAT CAST LINEHADD ADHESIVE HEREGPUMP SET SCREWPUMP SWITCH5b. If the Pump Off point does not match theone shown in char