A-C FIRE PUMP SYSTEMS
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
Series 1580 In-Line Mounted
Centrifugal Fire Pumps
Installation, Operation and Service Instructions
INSTRUCTION MANUAL
AC2516
DESCRIPTION
The Series 1580 Inline Centrifugal Fire Pump is a close
coupled pump which features high efficiency, rugged
construction, and in-line mounting. These features make
installation, operation and service easy to perform.
OPERATIONAL LIMITS
Unless special provisions have been made for your pump by
A-C Fire Pump Systems, the operational limits for Series
1580 Pumps are as follows:
MAXIMUM WORKING PRESSURE
Listed on pump nameplate.
SEAL OPERATING LIMITS
PACKING
PH Limitations 7-9; Temperature Range 0 to +200°F
For use on open or closed systems which require a large
amount of makeup water, as well as systems which are
subjected to widely varying chemical conditions and solids
buildup.
Vista de página 0
1 2 3 4 5 6 7 8

Resumo do Conteúdo

Página 1 - Centrifugal Fire Pumps

A-C FIRE PUMP SYSTEMSINSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.Series 1580 In-Line MountedCentrifugal Fire PumpsInstallation, Operation

Página 2 - INSTRUCTIONS

2SAFETYINSTRUCTIONSThis safety alert symbol will be used in this manual and on the unit safety instruction decals to draw attention to s

Página 3 - PUMP LOCATION

3PUMP LOCATIONLocate the pump so there is sufficient room for inspection,maintenance and service. If the use of a hoist or tackle isneeded, allow am

Página 4 - LUBRICATION

4PIPINGAlways install a section of straight pipe between the suctionside of the pump and first elbow or install an A-C FirePump S

Página 5 - FIGURE 5

5PRIMING AND STARTINGBefore starting the pump, the pump body must be full of liquid. Manual priming may be required if the system does notautomaticall

Página 6 - WITH PACKING

6SERVICE INSTRUCTIONS1. Close valves on suction and discharge sides of pump. (Ifno valves have been installed, it will be necessary to drainthe

Página 7 - RECOMMENDED SPARE PARTS

7CAPSCREW TORQUE (FOOT-POUND)CAPSCREW HEADCAPSCREW DIAMETERTYPE MARKING1/45/163/87/161/25/83/47/8 1SAE Grade 2 6 13 25 38 60 120 190 210 300BrassStain

Página 8 - Certified

© COPYRIGHT 1970, 2000 PRINTED IN U.S.A. 4-00USABell & Gossett8200 N. Austin AvenueMorton Grove, IL 60053Phone: (847) 966-3700Facsimile: (847) 966