A-C FIRE PUMP SYSTEMSINSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.Series 1580 In-Line MountedCentrifugal Fire PumpsInstallation, Operation
2SAFETYINSTRUCTIONSThis safety alert symbol will be used in this manual and on the unit safety instruction decals to draw attention to s
3PUMP LOCATIONLocate the pump so there is sufficient room for inspection,maintenance and service. If the use of a hoist or tackle isneeded, allow am
4PIPINGAlways install a section of straight pipe between the suctionside of the pump and first elbow or install an A-C FirePump S
5PRIMING AND STARTINGBefore starting the pump, the pump body must be full of liquid. Manual priming may be required if the system does notautomaticall
6SERVICE INSTRUCTIONS1. Close valves on suction and discharge sides of pump. (Ifno valves have been installed, it will be necessary to drainthe
7CAPSCREW TORQUE (FOOT-POUND)CAPSCREW HEADCAPSCREW DIAMETERTYPE MARKING1/45/163/87/161/25/83/47/8 1SAE Grade 2 6 13 25 38 60 120 190 210 300BrassStain
© COPYRIGHT 1970, 2000 PRINTED IN U.S.A. 4-00USABell & Gossett8200 N. Austin AvenueMorton Grove, IL 60053Phone: (847) 966-3700Facsimile: (847) 966